湖北11选5

For more product details, please call us:0731-84930888

HomeElectrical MeasurementThree-phase AC&DC Calibrators

TD4510 Calibrator for Three-Phase Apparatuses

适用于校准交流采样装置、交直流变送器、三相交直流电测仪表、同周期表、三相电能表等设备


准确度: 0.02 级 / 0.05 级可选

交流采样检测:可进行虚负荷校验 ( 标准源 ),或实负荷校验 ( 钳形夹测电流 )

变送器检测:检测电量变送器的基本误差,兼具直流纹波及响应时间的测量功能

谐波功能:三相电量可加载 2 ~ 21 次,幅度 / 相位均可调的谐波,进行谐波影响量试验


Overview

Model TD4510, a multi-function calibrator for electric power apparatuses。 Composed of three-phase and DC source, three-phase electrical parameters and DC signal measurement, electric energy measurement or other functions。 The optional accuracy classes of three-phase power are 0。02 and 0。05。

Applied to calibrate the AC sampling devices by real load or virtual load, and three-phase / DC apparatuses, AC electric energy meters, transmitters and synchrometers.

Meet the requirements of Q/GDW 1899-2013 Verification Regulation Calibration Specification of AC Sampling Electrical Measuring Equipment。 (Tunkia is involved in drafting)

Applications

1

2

Features

● AC Sampling Calibration: The virtual load calibration method is using by three-phase source, and the real load calibration method is using by measuring current with the clamp online.

● Transmitters Measurement: Measure the basic error, DC ripple and the response time for the transmitters.

 Harmonic Output: The output can load 2nd to 21st standard harmonics with adjustable amplitude and phase to test harmonic influence on the checked meters。

● Value Adjustment Method: Fixed-point, rotary encoder, step and potentiometer (option).

● Phasor Diagram: Freely adjust the phase between the three-phase electrical parameters, and intuitively display by phasor diagram.

● Excellent Human-Computer Interaction: Large LCD touch screen display, touch and button operation modes, easy for users to measure manually.

● Electric Energy Calibration (Option): Calibrate a single AC electric energy meter by the standard pulse I/O interface.

● Periodic Meters Calibration (Option): The fourth voltage output can calibrate the difference of amplitude, phase and frequency for periodic meters.

● Proprietary Software (Option): Support the calibration for the checked meters by semi-automatic or full-automatic, data management and report export.

Electrical Specifications

Three-Phase Voltage / Current Output

3

Output Characteristics

● Output Range of Voltage: 6 V to 456 V

 Output Range of Current: 20 mA to 12 A

● Resolution: 0.002 % of range

● Display: 6 digits

● Distortion: <0.2 %

● Protection: Short-circuit protection, open-circuit protection and overload protection.

Frequency, Phase, Harmonic and Symmetry Output

4

Three-Phase Power Output

5

Output Characteristics

● Output Range of AC Power: Combination of AC voltage range and AC current range.

● Range of Power Factor: -1.0000…0.0000…+1.0000

Three-Phase Voltage / Current Measurement

6

Measurement Characteristics

● Measuring Range of Voltage: 6 V to 456 V

● Measuring Range of Current: 0.1 A to 6 A

● Display: 6 digits

● Frequency: The range is from 45 Hz to 70 Hz, and the accuracy is ±0.01 Hz.

 Phase: The range is from 0.000 ° to 359.999 °, and the accuracy is ±0.1 °.

Three-Phase Power Measurement

7

Output Characteristics

8

● Output Range of Voltage: 10 mV to 660 V

● Output Range of Current: 0.1 mA to 11 A

● Resolution: 0.002 % of range

 Display: 6 digits

● Ripple Coefficient: <1 %

● Protection: Short-circuit protection, Open-circuit protection and overload protection.

DC Small Signal Measurement

9

AC Electric Energy (Option)

● Accuracy of Active Electric Energy:

±0.1 % of reading @ class 0.05; ±0.05 % of reading @ class 0.02;

● Accuracy of Reactive Electric Energy:

±0.2 % of reading @ class 0.05; ±0.1 % of reading @ class 0.02;

● Output of Standard Electric Energy Pulse: Full scale @ 60 kHz

● Input of Standard Electric Energy Pulse: Frequency ≤1 kHz, input level from 3 V to 12 V

● Constant of Electric Energy Meter: 1…1000000 imp./kwh or 1…1000000 imp./ws

The Fourth Voltage Output (Option for Synchrometer Calibration)

● Output Range of Voltage: 100 V and 380 V

● Output Margin of Voltage: 0 to 110 % of range

 Resolution: 0.002 % of range

● Accuracy in 1 Year: ±0.05 % of range

● Display: 6 digits

● Frequency: The range is from 45.000 Hz to 55.000 Hz, and the resolution is 0.001 Hz.

● Phase: The range is from 0.00 ° to 359.99 °, the resolution is 0.01 °, the accuracy is ±0.1 °.

General Specifications

● Line Power: 220 V ±22 V, 50 Hz ±2 Hz

● Operating Environment: 0 °C to +40 °C, 20 % to 80 % R·H, non-condensing

● Storage Environment: -20 °C to +70 °C, <80 % R·H, non-condensing

● Dimensions (W × H × D): 430 mm × 190 mm × 415 mm

 Weight: 18.5 kg

● Communication: RS-232 interface